Subject
ระบบปรับอากาศ
ประสิทธิภาพพลังงาน
สัมประสิทธิ์สมรรถนะ
รูปแบบการระบายความร้อนด้วยน้ำ
Air - conditioning Systems
Coefficient of Performance
Cooling Water Profile
Energy Efficiency
ปีที่ตีพิมพ์
2560
จำนวนเข้าชม 1
The purpose of this research was to investigate cooling water profile that effect to coefficient of performance of spilt type air- conditioning system. Air conditioner size of 12000 Btu/h was used in this experiment. There are three experiment of cooling water profiles in this work such as water spray water drop and heat exchanger profile. The ambient temperature conditions were controlled at 35 40 43 and 45 oC. The results of this study were found that heat exchanger profile had the highest average coefficient of performance and energy efficiency as 4.94 and 9.15 Btu/Wh which increased as 20.1% and 8.47% respectively when comparing with the normal working.