To Improvement the power factor is very important. Because the costs are increased or reduced. To Improvement the power factor the higher the value it is necessary to buildings offices and industrial buildings or the fact that the industry needs real power. And reactive power source to operate. This research presents the design and construction of reactive power factor control. Which amounted to 6 working order by the first sequence is divided into three three-phase electrical power system and three consecutive singles phase by active power different. first1 is reactive at 5 kVAr second 2 and third 3 are reactive at 2.5 kVAr forth 4 fifth 5 and sixth 6 precious marine active 0.83 kVAr control. the power factor controller that controls RG3-12 pay Oval active in various sequences. As a result when not equipped with reactive power compensation software to control the power factor. This makes the flow of the high and low Power Factor schedule. When equipped compensate reactive power source to power factor control. Single-phase motor 1 kW and light bulb 1640-watt making the current decline of 14 amps rest 12 amps of the power factor increases from 0.5 to 0.929. When connected to three-phase motor with 2 kW 0.8 2.2 flow down from 2.360 rests 0.942 amps of power factor value up from 0.308 to 1.0.