การต่อลงดินของระบบไฟฟ้าเพื่อลดผลกระทบของแรงดันไฟฟ้าตกชั่วครู่ที่เกิดจากการลัดวงจรแบบหนึ่งเฟสลงดิน
The faults in a power distribution system do not only impact to power outage directly. They also cause voltage sag problem spread over the system. A single-line to ground fault is about 70% of the overhead system faults. The magnitude and duration of voltage sag causes the economic damage of the system. This paper presents an analysis of the different systems grounding to mitigate the voltage sag in a power distribution system by using the technical analysis system in case of one phase to ground fault. The objective is to minimize voltage drop for users using the simulation with single line to ground fault in distribution system voltage level at 22 kV PEA’s test system by the computer program. The results show that the grounding method can mitigate the voltage sag and reduce the damage of the economic system.
Design and Construction High Voltage,High Frequency Transformer Rated 500 kV 250 kHz
This project design and constructions high voltage high frequency transformer or tesla transformer. The tesla transformer is design at 500 kV rating voltage and 250 kHz resonant frequency. By coupling air axle and have the air are the electric insulator between primary coil and secondary coil Which primary coil test at 60 degree Group part spark gap is will the Electrostatic gap. This paper propose and consider high voltage high frequency transformer at 500 kV and 250 kHz rated. For use a transformer aforementioned is the equipment for test flash over prenouaena of porcelain insulator and electric insulation.